Limits for liquids kept outside cabinets the total amount of liquids that may be kept outside a storage cabinet or storage room are listed at 29 cfr 1910 106 e 2 ii b.
Flammable liquids cabinet regulations.
These limits are only applicable to those portions of an industrial plant where the use and handling of flammables is only incidental to the principal business.
Not more than three such cabinets may be located in a single storage area.
Not more than 60 gallons of category 1 2 and or 3 flammable liquids or 120 gallons of category 4 flammable liquids shall be stored in any one storage cabinet.
1926 152 b 4 i.
Quantities in excess of this shall be stored in an inside storage room.
The quantity of liquid that may be stored outside of an inside storage room or storage cabinet in a building or in any one fire area of a building cannot exceed.
According to the national fire protection association nfpa code 30 flammable and combustible liquids code venting a flammable storage cabinet is not necessary for fire protection purposes.
You may not store more than 60 gallons of category 1 2 or 3 flammable chemical liquids within.
Flammable and combustible liquid storage cabinets are designed to help protect the internal contents from a fire outside of the cabinet.
Flammable and combustible liquids code enforceable under osha and many state and local regulations nfpa 30 provides safeguards to reduce the hazards associated with the storage handling and use of flammable and combustible liquids.
And up to three safety cabinets are allowed in a storage area.
For example no safety cabinet is required to store less than 25 gallons of category 1 flammable liquids in approved containers.
Not more than 60 gallons of flammable or 120 gallons of combustible liquids shall be stored in any one storage cabinet.
Quantities in excess of this shall be stored in an inside storage room.
The minimum separation between a liquefied petroleum gas container and a flammable liquid storage tank shall be 20 feet except in the case of flammable liquid tanks operating at pressures exceeding 2 5 p s i g.
In addition you may not store more than 120 gallons of category 4 flammables in your storage cabinet.
In which case the provisions of subdivisions a and b of this subdivision shall apply.
The limit for a single storage cabinet is 60 gallons of category 1 2 or 3 flammable liquids or 120 gallons of category 4 flammable liquids.
25 gallons of category 1 liquids in containers 120 gallons of category 2 3 or 4 liquids in containers 660 gallons of category 2 3 or 4 liquids in a single portable tank.
Flammable and combustible liquid storage cabinets are designed to protect the internal contents from a fire outside the cabinet.
Or equipped with emergency venting which will permit pressures to exceed 2 5 p s i g.